MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTORMOTOR- UND GERÄTESCHUTZSCHALTER
Product description
The AS168X is a thermal magnetic high performance CBE to IEC 934and a «supplementary protector» to UL 1077. It is capable of drasti-cally limiting the «let-through energy» in case of short circuit interrup-tions. The series is available in units from one to four poles for use inAC and DC circuits. Multipole devices are connected internally and atthe handle for simultaneous operation. This applies also to combina-tions with the switched neutral pole. Well designed screw type term-inals at line and load side are provided for safe and easy connectionto line and load. They accept #16 to 4 AWG / 1,5 to 25 mm2.The AS168X is suitable as supplementary protector under UL 1077 / EN 60934 or as Manual Motor Controller according UL 508 / CSA 22.2 14. Thus the Breaker has a high versatility and is suitable for many functions:
• Motor overload protection (thermal and magnetic)• Motor starting across-the-line (direct-on-line)
• Motor starting with motor disconnect (cos phi 0,4–0,5)• Motor group installation (short capacity 5 kA)• Control circuits
AS168X
Produktebeschreibung
Der AS168X ist ein thermisch magnetischer Hochleistungs CBE, derin der Lage ist, bei Kurzschluss-Abschaltungen den Durchlass-Stromdrastisch zu reduzieren. Die Serie ist erhältlich in Ausführungen miteinem bis vier geschützten Polen, die in Wechselstrom- oder Gleich-stromnetzen eingesetzt werden können. Mehrpolige CBE sind internund beim Kipphebel mechanisch verbunden, um gleichzeitiges Schal-ten zu gewährleisten. Dies gilt auch für eine Kombination mit demschaltbaren Null-Leiter Pol. Raffiniert konstruierte Liftklemmen auf derEingangs- und Abgangsseite ermöglichen einen bequemen Netz- undLastanschluss. Die Klemmen sind zum Anschluss von Leitern mit 1,5bis 25 mm2Querschnitt geeignet, (AWG #16...4).
Der AS168X ist einsetzbar als Geräteschutzschalter nach UL 1077 /EN 60934 oder als Motorschutzschalter nach UL 508 bzw.
CSA 22.2 14. Der Schalter ist somit vielseitig einsetzbar und eignetsich für folgende Funktionen:
• Motor overload protection (thermisch und magnetisch)• Motor starting across-the-line (direct-on-line)
• Motor starting with motor disconnect (cos phi 0,4–0,5)• Motor group installation (short capacity 5 kA)• Control circuits
Accessories
•Auxiliary contact module
Each auxiliary contact module contains one contact, either normally open or normally closed.
•Signal contact module
Signal contact modules are linked internally with the protected poles but not linked at the handles.
Contacts are actuated by a fault condition at the protected poles, not by the manual operation of the CBE.•Relay trip module
The relay trip module can be used for remote tripping of the adjacent poles by applying a voltage to the module’s terminal.•Switched neutral pole (factory assembled)
This module allows to automatically open the neutral line when the protected poles have been tripped.
Zubehör
•Hilfskontakte
Jedes Modul ist mit einem Öffnungs- oder Schliesskontakt ausgerüstet.•Signalkontakt-Modul
Signalkontakt Module sind intern mit dem benachbarten Pol verbunden, weisen aber keine Verbindung der Kipphebel auf. Daher schaltet dieses Modul nur beim automatischen Auslösen der benachbarten Pole, aber nicht bei manueller Betätigung.•Fremdauslösung
Dieses Modul kann für die Fernauslösung der benachbarten Pole mittels eines Spannungspulses verwendet werden.•Schaltbarer Neutralleiter Pol
Dieses Modul erlaubt ein automatisches Öffnen des Neutralleiters wenn die geschützten Pole auslösen.
Features••••••
Excellent short circuit performance (up to 10 kA)
High limits of discrimination (due to energy limitation)Wide choice of characteristics (Adaptability)Availability of AC and DC in the same frame sizeCompact, «finger safe» designEase installation (on DIN rail)
Besondere Merkmale
•Exzellentes Abschaltvermögen (bis zu 10 kA)
•Ermöglicht hohe Selektivitätsgrenzen durch energiebegrenzendesSchalten
•Grosse Auswahl von Auslösekennlinien
Anpassungsfähigkeit an die Applikations-Bedingungen•Ausführungen für Wechsel- und Gleichstrom in gleicher Gehäusegrösse
•Kompakte «fingersichere» Bauweise•Einfache Montage (DIN-Schiene)
Applications
• Industrial machines • Automation
• Aircondition, ventilation• Transformers• Power supplies• Telecom systems• Computer systems• Test systems
• Medical equipments
Anwendungen
• Industrieller Maschinenbau• Automation
• Klima- und Ventilationsanlagen• Transformatoren• Stromversorgungen
•Telekommunikationsanlagen• Computersysteme• Testsysteme• Medizinalgeräte
www.schurter.com123
元器件交易网www.cecb2b.com
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTORMOTOR- UND GERÄTESCHUTZSCHALTER
Effect of ambient temperature
AC-breakers are calibrated for an ambienttemperature of +40°C, DC-breakers for+23°C. To determine the rated current for a lower or higher ambient temperature, use a correction factor from the table below:
AS168X
Einfluss der
Umgebungstemperatur
AC-Schalter sind für eine Umgebungs-temperatur von +40°C geeicht, DC-Schalterfür+23°C.Zur BestimmungdesNennstromesfür eine tiefere oder höhere Umgebungs-temperatur ist ein Korrekturfaktor gemässuntenstehender Tabelle zu verwenden:Umgebungs-temperatur [°C]
Korrekturfaktor
AC-VersionDC-Version
Ambient
temperature [°C]Correction factor
AC versionDC version
–20 0,78 0,80–5 0,82 0,870 0,83 0,90+10 0,87 0,95+23 0,91 1,00+30 0,95 1,05+40 1,00 1,10+50 1,05 1,20+60 1,11 1,30
–20 0,78 0,80–5 0,82 0,870 0,83 0,90+10 0,87 0,95+23 0,91 1,00+30 0,95 1,05+40 1,00 1,10+50 1,05 1,20+60 1,11 1,30
Example DC version:Rated current at +23°CAmbient temperatureCorrection factor
Chosen rated current at+50°C ambient temperature10 A x 1,2 = 12 A
10 A+50°C1,2
Beispiel DC-Version:Nennstrom bei +23°CUmgebungstemperaturKorrekturfaktor
Gewählter Nennstrom bei +50°C Umgebungstemperatur10 A x 1,2 = 12 A
10 A+50°C1,2
Tripping characteristic FAuslösekennlinie F
1hr1000sTripping characteristic GAuslösekennlinie G
1hr1000sTripping characteristic HAuslösekennlinie H
1hr1000s100s100s100s10s10s10s1s1s1s0,1s0,1s0,1sTripping time / AuslösezeitTripping time / Auslösezeit1ms1msTripping time / Auslösezeit1101001000 x In
10ms10ms10ms1ms0,1ms1101001000 x In
Multiple of rated current (x In)Nennstrom-Vielfaches (x In)
0,1msMultiple of rated current (x In)Nennstrom-Vielfaches (x In)
0,1ms1101001000 x In
Multiple of rated current (x In)Nennstrom-Vielfaches (x In)
124www.schurter.com
元器件交易网www.cecb2b.com
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTORMOTOR- UND GERÄTESCHUTZSCHALTER
AS168X
Tripping characteristic DFTripping characteristic DGTripping characteristic DHAuslösekennlinie DF
Auslösekennlinie DG
Auslösekennlinie DH
1hr1hr1hr1000s1000s1000s100s100s100s10s10s10s1s1s1s0,1s0,1s0,1sti10msti10msti10mseeezzzeeesssööölllsssuuuAAA / e1ms // e1mse1msmmmiiittt gggnnniiippppppi0,1msi0,1msiTrTrTr0,1ms1101001000 x In
1101001000 x In
1101001000 x In
Multiple of rated current (x In)Multiple of rated current (x I)Nennstrom-Vielfaches (x In)Multiple of rated current (x In)
Nennstrom-Vielfaches (x INennstrom-Vielfaches (x Inn)
n)
Technical data/ Technische DatenPole / Pole:Rated voltage UeAC versions / AC Versionen F; G; HAC 480/277 V; DC 65 VNennspannung UeDC versions / DC Versionen DF; DG; DHDC 180 V 1 pole/ 1poligDC 360 V 2 – 3 pole/ 2 – 3poligNote: The connection polarity must be strictlyobserved. An application with a DC Type AS168Xin an AC network is not allowed.Hinweis: Die Anschlusspolarität muss unbedingtbeachtet werden. Eine Anwendung von DC Versionen in AC Netzen ist nicht zulässig.Rated current ISee approvals, page 126AC/DC 0,5 – 52 ANennstrom InnSiehe Approbationen Seite 126AC/DC 0,5 – 52 AEnduranceNumber of cycles at I6000LebensdauerAnzahl Schaltspiele bei Inn6000Type of tripping• Thermal magnetic/ thermisch-magnetischTMAuslöseart• Positively trip-free/ positive FreiauslösungType of actuation/ BetätigungsartManual ON/OFF/ Manuell EIN/AUSS-type/ S-TypPermissible wire cross section1,5 – 25 mm2/AWG #16...4Zulässiger Leiterquerschnitt1,5 – 25 mm2/AWG #16...4Switched neutral / Schaltbarer, neutraler Pol:Rated voltage UAC 277 VRated currentIe/ Nennspannung U/ Nennstrom Ien nAC/DC 65 AFunctionThe switched neutral closes with manual closure of the poles and opens automatically with thermal magnetic tripping of the poles.www.schurter.com125
元器件交易网www.cecb2b.com
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTORMOTOR- UND GERÄTESCHUTZSCHALTER
Technical data (continued) / Technische Daten (Fortsetzung)Funktion Der Neutralleitertrenner schliesst beimanueller Einschaltung der Pole undöffnet automatisch bei thermisch-magnetischer Auslösung der Pole.AS168X
Add-on modules/ Zusatzmodule:Rated voltage Ue/ Nennspannung UeAC 277 VDC 125 VDC 50 VType H1 (assumes the same contact position)Type H2 (assumes the opposite position)Typ H1 (gleichschaltend)Typ H2 (gegenschaltend)Rated current In/ Nennstrom In6 A1 A6 AActuation of the contact is determinedby the condition of the handle positionof the adjacent poles.Hilfskontakte schalten bei thermisch-magnetischer Auslösung sowie Handbetätigung synchron mit den geschützten Polen.The signal contact operates due to a thermal magnetic tripping and mustbe reset by hand.Signalkontakte schalten nur beithermisch-magnetischer Auslösungund sind von Hand zurückzustellen.Impedance at 50 HzImpedanz bei 50 Hz1.1 Ω4.7 Ω16 Ω63 Ω395 ΩWhen voltage is applied across the terminals, remote tripping takes place by a self interrupting magnetic system. Trip delay time 8 - 16 ms.Beim Anlegen der Klemmenspannungerfolgt die Auslösung durch ein selbstunterbrechendes Magnetsystem.Ausschaltverzögerung 8 – 16 ms.Auxiliary contact H1 & H2 andSignal contact S1 & S2Hilfskontakt H1 & H2 und Signalkontakt S1 & S2Functional auxiliary contact moduleFunktion HilfskontaktFunctional signal contactType S1 (assumes the same contact position)Type S2 (assumes the opposite position)Typ S1 (gleichschaltend)Typ S2 (gegenschaltend)Funktion SignalkontaktRelay trip moduleFremdauslösungTypeTypA1A2A3A4A5Voltage range AC/DCArbeitsbereich AC/DC5 – 12 V10 – 24 V20 – 48 V40 – 110 V90 – 240 VFunction of relay trip moduleFunktion FremdauslösungGeneral data/ Allgemeine Daten:Dielectric strengthSpannungsfestigkeitVibration resistanceSchwingungsfestigkeitShock resistance/ StossfestigkeitProtection against electric shockBerührungsschutzPermissible ambient temperatureZul. UmgebungstemperaturWeight/ Gewichte1 pole / 1-PolSwitched neutral/ Schaltbarer neutraler PolAuxiliary contact/ HilfskontaktSignal contact/ SignalkontaktRelay trip module/ FremdauslösungIEC 60068-2-6, Test FcAC 2000 VAC 2000 V0,75 mm amplitude, 10 – 57 Hz0,75 mm Amplitude, 10 – 57 Hz25 g / 10 ms HalfsinusIP20IP20-20°C to +60°C-20°C bis +60°Cca. 130 gca. 130 gca. 100 gca. 100 gca. 120 gIEC 60068-2-27, Test EaFinger safe per IEC 529Fingerschutz nach IEC 529126www.schurter.com
元器件交易网www.cecb2b.com
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTORMOTOR- UND GERÄTESCHUTZSCHALTER
AS168X
Approvals / Approbationen
AC versions / AC-Versionen
DVEVDEULULEN 60934 *UL 1077UL 508 **CSA 22.2 235CSA 22.2 14PolesCharacteristic/Volt ACVoltIcn [A]Volt ACVolt DCIcn [A]Volt ACIcn [A]Nennstrom [A]DC1F / G / H420/24065450027765 5000277500045 - 52F / G420/240654500277 500027750000.5 - 252406510000H420/24065450027765 500027750000.5 - 40F / G420/240654500277 5000277500027 - 4024065100002F / G / H42065450048065 5000480500045 - 52F / G420654500480651000048050000.5 - 25H42065450048065 500048050000.5 - 40F / G4206545004806510000480500027 - 403F / G / H420654500480Y/27765 5000480500045 - 52F / G420654500480Y/277651000048050000.5 - 25H420654500480Y/27765 500048050000.5 - 40F / G420654500480Y/2776510000480500027 - 404F / G / H420/240654500480Y/27765 5000480Y/27750000.5 - 52DC versions / DC-Versionen
DVEVDE *ULEN 60934UL 1077CSA 22.2 235PolesCharacteristic/Volt DCIcn [A]Volt DCIcn [A]Nennstrom [A]1DF / DG120450018020000.5 - 50DH120450018020006 - 502DF / DG240450036020000.5 - 50DH240450036020006 - 503DF / DG3604500360100000.5 - 40DF / DG3604500360500045 - 50DH360450036050006 - 504DF / DG3604500360100000.5 - 40DF / DG3604500360500045 - 50DH360450036050006 - 50* VDE approval pending/ VDE Zulassung pendent
** Rated currents 32–52 A available approx. March 2003/ Nennwerte 32–52 A ca. ab März 2003 lieferbar
www.schurter.com
127
元器件交易网www.cecb2b.com
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTORMOTOR- UND GERÄTESCHUTZSCHALTER
AS168X
Conversion table Ampere rating – Horsepower rating/ Umrechnungstabelle Ampère – HorsepowerVoltage Rating:
One pole:Two pole:Three pole:
AC 277 V, 1 phase
AC 480Y/277 V, 1 phaseAC 480Y/277 V, 3 phase
HORSEPOWER
(FLA & LRC RATINGS APPLY WHERE NO HP RATING IS GIVEN)
NOMINAL CIRCUIT VOLTAGE, Vac
380-440-220-110-265277200208
415480240120
1
2 pole
pole
1/101/61/41/31/23/411 1/2222333355557 1/27 1/2HP-Rating: 1 phase (1 pole & 2 pole):
AS168X-CBMOTOR NAMEPLATE
Rated Current(See Note #1)
0.5A1A1.5A2A3A4A5A6A7A8A9A10A12A13A15A16A18A20A23A25A27A30AFLARating0.5A1A1.5A2A3A4A5A6A7A8A9A10A12A13A15A16A18A20A23A25A27A30AStarting/LRC Rating
3°6°9°12A18A24A30A36A42A48A54A60A72A78A90A96A108A120A138A150A162A180A1/101/81/61/41/41/31/31/21/21/23/4111 1/21 1/22221/61/41/31/21/23/43/411 1/21 1/2222333331/61/31/31/21/23/4111 1/21 1/2222333331/101/81/41/31/21/23/4111 1/222223333351/101/61/41/31/23/4111 _1 1/222333335551/101/61/31/31/23/4111 1/2222333335551/211 1/2222333355557 1/27 1/21010HP-Rating: 3 phase (3 pole):
AS168X-CB
MOTORNAMEPLATEFLARating0.5A1A1.5A2A3A4A5A6A7A8A9A10A12A13A15A16A18A20A23A25A27A30A
Starting/LRC Rating
HORSEPOWER
(FLA & LRC RATINGS APPLY WHERE NO HP RATING IS GIVEN)
NOMINAL CIRCUIT VOLTAGE, VAC
110-120200208220-240380-415440-4803 pole
Rated Current
(See Note #1)
0.5A1A1.5A2A3A4A5A6A7A8A9A10A12A13A15A16A18A20A23A25A27A30A
10A12.5A20A25A32A32A32A46A46A46A63.5A63.5A81A81A81A81A116A116A145A145A
1/21/23/43/4111 1/21 1/222233333
1/23/4111 1/2222333355557 1/27 1/21/23/4111 1/222233335557 1/27 1/27 1/21/23/411 1/222233335557 1/27 1/27 1/210
1/23/411 1/2223335557 1/27 1/21010101015151/23/41 1/223335557 1/27 1/21010101015152020
Note #1: For AC motor circuit nameplate FLA loads, AC general-use loads, AC resistance loads
128www.schurter.com
元器件交易网www.cecb2b.com
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTORMOTOR- UND GERÄTESCHUTZSCHALTER
AS168X
Order code/ Bestellcode
Basic type/ Grundtyp
Thermal magnetic high performance circuit breaker
Thermisch-magnetischer Hochleistungs-GeräteschutzschalterNumber of poles/ Polzahl1234
Tripping characteristics/ Auslösekennlinien
ThermalMagneticDeliverable currentsThermischMagnetischLieferbare NennströmeF1.0–1.25 xI3 – 5 xI0,5 – 52 AG1.0–1.25 xIn6 – 10 xIn0,5 – 52 AH1.0–1.25 xIn12 – 20 xIn0,5 – 52 ADF1.05–1.35 xIn4,5 – 8 xIn0,5 – 50 ADG1.05–1.35 xIn9 – 16 xIn0,5 – 50 ADH
1.05–1.35 xInn
18 – 32 xInn
6,0 – 50 A
Rated current/ NennstromCodeIn(A)CodeIn(A)CodeIn(A)CodeIn(A)0050.50606.016016.032032.00101.00707.018018.035035.00151.50808.020020.040040.00202.00909.023023.045045.00303.010010.025025.050050.00404.012012.027027.0520
52.0*
050
5.0
150
15.0
300
30.0
* AC version only/ Nur AC-Version
Switched neutral pole /Schaltbarer neutraler PolN
AS168X – CB2DG200NMaximum222HHHcombination 1,1,1,HHHMaximale ///AS168X – ACBS2222SSS Kombinationen1,1,1,SSS ///555 A A A......1. 1. 1. AAA1 Add-on module +4 poles +N2 Add-on modules +3 poles +N1 Zusatzmodul +4 Pole +N2 Zusatzmodule +3 Pole +NAuxiliary contact/ HilfskontaktH1Assumes the same contact position as the protected poles
Gleiche Kontaktposition wie die geschützten Pole (gleichschaltend)H2
Assumes the opposite contact position as the protected poles
Entgegengesetzte Kontaktposition wie die geschützten Pole (gegenschaltend)
Signal contact/ SignalkontaktS1Assumes the same contact position as the protected poles
Gleiche Kontaktposition wie die geschützten Pole (gleichschaltend)S2
Assumes the opposite contact position as the protected poles
Entgegengesetzte Kontaktposition wie die geschützten Pole (gegenschaltend)
Relay trip module/ FremdauslösungA1AC/DC 5 – 12 VA2AC/DC 10 – 24 VA3AC/DC 20 – 48 VA4AC/DC 40 – 110 VA5
AC/DC 90 – 240 V
Accessories / Zubehör
Must be ordered separately/muss separat bestellt werden
www.schurter.com129
元器件交易网www.cecb2b.com
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTORMOTOR- UND GERÄTESCHUTZSCHALTER
DIN rail mounting / Hutschiene DIN-Befestigung
AS168X-CB1…
45AS168X
…N
44.461.668.426.65.1351.99035 mm DIN rail EN 5002235 mm Hutschiene DIN-EN 5002217.5– 0.0+0.517.5– 0.0+0.5Max. torqueMax. zulässiges AnzugsdrehmomentWire crosssectionDrahtquerschnitt1.5…10 mm2 16 …25 mm2 AWG #16...8AWG #6...4
Max. torque
Max. Drehmoment2.5 Nm3.1 Nm22 Ib–in28 Ib–in
AS168X-ACBH.AS168X-ACBS.AS168X-ACBA.
909017.5– 0.0+0.517.5– 0.0+0.517.5– 0.0+0.5130www.schurter.com
9026.6元器件交易网www.cecb2b.com
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTORMOTOR- UND GERÄTESCHUTZSCHALTER
Schematic diagrams / Schaltbilder
AS168X
AS168X-CB1…
AS168X-CB1…N
AS168X-CB1…AS168X-ACBH1AS168X-CB1…AS168X-ACBH2
AS168X-CB1…AS168X-ACBS1AS168X-CB1…AS168X-ACBS2AS168X-CB1…AS168X-ACBA.
Accessories/ Zubehör
AS168X-ACBLOA
Lockout attachment/ Abschliessverriegelung